Public Utilities Code section 1626
(a)
Name and address of school facility and person or contractor preparing and certifying assessment report.(b)
Documentation of HVAC equipment model number, serial number, general condition of unit, and any additional information that could be used to assess replacement and repair options given potential for increased energy efficiency benefits.(c)
Either verification that MERV 13 filters have been installed or verification that the maximum MERV-rated filter that the system is able to effectively handle has been installed and what that MERV-rating is.(d)
The verified ventilation rates for facility classrooms, auditoriums, gymnasiums, nurses’ offices, restrooms, offices, and other occupied areas, and whether those rates meet the requirements set forth in Table 120.1-A. If ventilation rates do not meet applicable requirements, then an explanation for why the current system is unable to meet those rates shall be provided.(e)
The verified exhaust for facility classrooms, auditoriums, gymnasiums, nurses’ offices, restrooms, and other occupied areas and whether those rates meet the requirements set forth in the design intent.(f)
Documentation of system deficiencies and recommendations for additional maintenance, replacement, or upgrades to improve energy efficiency, safety, or performance.